Ajout config SNMP pour APC avec compteurs par prise
This commit is contained in:
parent
dcadc1e029
commit
3c44420915
|
@ -188,14 +188,43 @@ LoadPlugin snmp
|
||||||
Instance "apc_current_overload"
|
Instance "apc_current_overload"
|
||||||
Values ".1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.1"
|
Values ".1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.1"
|
||||||
</Data>
|
</Data>
|
||||||
|
# Pour les APCs avec compteurs par prises
|
||||||
|
<Data "apc_outlet_current">
|
||||||
|
Type "current"
|
||||||
|
Table true
|
||||||
|
Instance ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.1"
|
||||||
|
Scale 0.1
|
||||||
|
Values ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.6"
|
||||||
|
</Data>
|
||||||
|
<Data "apc_outlet_watt">
|
||||||
|
Type "energy"
|
||||||
|
Table true
|
||||||
|
Instance ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.1"
|
||||||
|
Values ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.7"
|
||||||
|
</Data>
|
||||||
|
<Data "apc_outlet_total_energy">
|
||||||
|
Type "energy_wh"
|
||||||
|
Table true
|
||||||
|
Instance ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.1"
|
||||||
|
Scale 0.1
|
||||||
|
Values ".1.3.6.1.4.1.318.1.1.26.9.4.3.1.11"
|
||||||
|
</Data>
|
||||||
|
|
||||||
<Host "APC">
|
|
||||||
|
<Host "APC classique">
|
||||||
Address "192.0.2.2"
|
Address "192.0.2.2"
|
||||||
Version 2
|
Version 2
|
||||||
Community "public"
|
Community "public"
|
||||||
Collect "apc_current_load" "apc_current_low" "apc_current_near" "apc_current_overload"
|
Collect "apc_current_load" "apc_current_low" "apc_current_near" "apc_current_overload"
|
||||||
Interval 1800
|
Interval 1800
|
||||||
</Host>
|
</Host>
|
||||||
|
<Host "APC avec compteurs par prises">
|
||||||
|
Address "192.0.2.2"
|
||||||
|
Version 2
|
||||||
|
Community "public"
|
||||||
|
Collect "apc_current_load" "apc_current_low" "apc_current_near" "apc_current_overload" "apc_outlet_current" "apc_outlet_watt" "apc_outlet_total_energy"
|
||||||
|
Interval 1800
|
||||||
|
</Host>
|
||||||
|
|
||||||
# ATS
|
# ATS
|
||||||
<Data "ats_input_freq_a">
|